Distribution Automation Terminals
GP3415
The GP3415 integrates line protection and communication equipment management in a modular plug-in chassis with flexible configuration and independent protection modules. It is suitable for substations, indoor and outdoor switching stations, distribution rooms, disconnector rooms and box-type substations.
Collects, processes and analyzes real-time distribution-network measurements and remote-signaling data so the dispatch center can monitor network conditions and make operating decisions. Remote control enables equipment operations from the control center, shortening fault-handling time and reducing labor intensity.
Enquire About This Product01 / PRODUCT FEATURES
Product at a glance
High-precision, Wide-range Sampling
- Supports analog measurement with electronic VT + electronic CT or electronic VT + electromagnetic CT configurations, meeting metering, measurement and protection requirements simultaneously.
Local Earth-fault Location and Isolation
- Uses transient-based algorithms to locate and isolate single-phase earth faults locally in small-current, non-effectively grounded systems.
Local Feeder Automation
- Supports local feeder automation compatible with recloser-based voltage-time, voltage-current-time and adaptive integrated modes.
Remote Configuration and File Upload
- Extended communication protocols support remote parameter configuration and upload of remote-control records, logs, waveform recordings and energy metering files.
Flexible Cascade Communication
- Four field-switchable RS232/RS485 serial ports and two RJ45 Ethernet ports meet complex on-site communication requirements.
Testing and Commissioning
- Covers type testing, specialist distribution-terminal testing, primary-secondary integration testing, pre-supply sample submission, full delivery inspection, on-site joint commissioning and operational evaluation.
02 / SPECIFICATIONS
Technical specifications
| Description | Value |
|---|---|
| Model | GP3415 |
| Operating Environment | Ambient temperature: -40°C~+70°C; maximum temperature change rate: 1°C/min Relative humidity: 10%~95%; maximum absolute humidity: 35g/m³ Atmospheric pressure: 70~110kPa |
| Power Supply | Nominal DC 24V; allowable input range: 21~29V |
| Switch Measurement & Control Capacity | 48-channel remote-signaling input; 16-channel remote-control output 8-channel AC analog voltage input; 24-channel AC analog current input |
| IP Rating | IP41 |
| Communication Interface | 2×RS232 + 2×RS485 + 2×RJ45 |
| Communication Protocol | DNP3.0, IEC60870-5-101, IEC60870-5-104, IEC61850, IEC62351, MODBUS |
| Measurement Accuracy | Current/voltage: Class 0.2 Power and power factor: Class 1 SOE resolution: ≤2ms Frequency: 0.005Hz Remote signaling response: <1s Telemetry response: <1s Remote control response: <1s |
| Timekeeping Accuracy | Time error: <2s per 24h |
| Rated Frequency | 50Hz / 60Hz |
| Voltage & Current Sampling | PT: 110/√3 V; CT: 1A/5A 1.2Un, continuous operation 1.2In, continuous operation |
| Dimensions (W × D × H) | 332.92 × 151.00 × 177.00mm |
Electromagnetic Compatibility Tests
| Test Item | Test Standard | Test Level / Duration |
|---|---|---|
| Electrostatic discharge immunity | IEC61000-4-2 | Level IV |
| Radiated radio-frequency electromagnetic field immunity | IEC61000-4-3 | Level IV |
| Electrical fast transient/burst immunity | IEC61000-4-4 | Level IV |
| Surge immunity | IEC61000-4-5 | Level IV |
| Power-frequency magnetic field immunity | IEC61000-4-8 | Level V |
| Conducted radio-frequency disturbance immunity | IEC61000-4-6 | Level III |
| Damped oscillatory magnetic field immunity | IEC61000-4-18 | Level III |
| Voltage sag | IEC61000-4-29 | 0.1s |
| Voltage interruption | IEC61000-4-29 | 0.05s |
| DC ripple immunity | IEC61000-4-17 | Level III |