Product at a glance

High-accuracy Multi-type Energy Metering

  • Uses a Vango V9911 MCU + V9203 metering chip to measure import and export active and reactive energy.
  • Active energy accuracy Class 1 and reactive energy accuracy Class 2. Starting current ≤0.004Ib; overload withstand current 30Imax for 0.01s.

Comprehensive LCD Information

  • The LCD displays remaining energy, total active energy, voltage, current, frequency, power factor, energy for four tariffs, maximum demand, date and time.

Flexible Communication Options

  • Standard RS-485 interface with expandable infrared and remote 4G communication. Compatible with DL/T645-2007 and MODBUS-RTU protocols.

Reliable Switching Control

  • Direct-connected versions have a built-in 80A magnetic latching relay for disconnection and reconnection. Transformer-operated versions support external switch on/off control.

Long Data Retention and Low Power Consumption

  • Data retention exceeds 20 years, with internal power consumption ≤2W / 10VA. Operating frequency is 50/60Hz ±10% and operating voltage is Un ±10%.

Durable Protective Construction

  • The base uses flame-retardant ABS. The transparent upper window and terminal cover use flame-retardant, impact-resistant polycarbonate. The terminal block uses glass-fiber-reinforced polycarbonate, and terminals use nickel-plated 95 brass.
  • IP51 dust and water protection with Class II instrument insulation enclosure.
02 / SPECIFICATIONS

Technical specifications

DescriptionValue
Energy Metering Accuracy
Active Class 1; reactive Class 2
Reference Voltage (Un)
3 × 220/380V
Operating Voltage
Un ±10%
Rated Current (Ib)
1.5A / 5A / 10A / 15A / 20A / 30A
Maximum Current (Imax)
20A / 40A / 60A / 80A / 100A
Starting Current
≤0.004Ib
Overload Withstand Current
30Imax for 0.01s
Operating Frequency
50/60Hz ±10%
Internal Power Consumption
≤2W / 10VA
Pulse Constant
400 imp/kWh; 6400 imp/kWh
Data Retention
>20 years
Operating Humidity
≤75%
Storage Humidity
≤95%
Operating Temperature
-10°C to +50°C
Storage Temperature
-30°C to +70°C
Dust and Water Protection
IP51
Protective Insulation Enclosure
Instrument Class II