| Rated voltage | 3x57.7/110V~3x240/415V |
|---|
| Operating voltage range | 80%Un~120%Un |
|---|
| Meter secondary rated current & Starting Current | 1(6)A; Starting current: 0.1%Ib |
|---|
| Max. Primary measurable current (with external CT) | Up to 3000A for billing application; up to 6000A for sub-monitoring only (depends on matched external CT) |
|---|
| Rated frequency | 50Hz |
|---|
| Pulse Constant | 10000imp/kWh 10000imp/kvarh |
|---|
| Accuracy Class | Cl.0.5S for Active Cl.1 for Reactive |
|---|
| Power Consumption | Voltage circuit < 1W or 5VA, Current circuit < 0.2VA |
|---|
| Battery and Life | Replaceable Lithium battery, life more than 15 years |
|---|
| Tropical working temperature | -40℃ to +70℃, Humidity is up to 95% |
|---|
| EMC Performance | Impulse voltage > 8kV, AC voltage > 4kV, Short circuit current > 3kA, Electrostatic Discharge > 8kV&15kV etc. |
|---|
| Protection class | IP54 comply with IEC60529 Insulation grade II |
|---|
| Housing material | Polycarbonate with non-conductive, high impact, smooth finish, durable, non-flammable, UV stabilized, UV resistant and high resistance to weathering |
|---|
| Dimension | Meter: 294mmX170mmX81mm |